Home  /  Engineering Resources  /  Control Cabinet Fan Selection Example

Control Cabinet Fan Selection Example

This worked example uses hypothetical cabinet conditions and actual Hongbo catalogue data. A buyer needs about 40 CFM through a filtered 120 mm opening and must decide which catalogue model is worth testing in the closed cabinet.

120x120x38mm AC Axial Fan
Published Hongbo 12038-7P fan. The cabinet and duty values are example inputs.

Set the airflow and installation limits

Heat load and allowable rise

Assume 220 W of equipment losses and a 10 K temperature rise. The rough ventilation estimate is 3.1 × 220 ÷ 10 = 68.2 m³/h, or about 40 CFM. This screening estimate assumes that the heat is removed by the ventilation air. The installed temperature still needs to be verified.

Cabinet and supply

Assume a nominal 120 mm mounting position, up to 40 mm of fan-body depth and a 100/125 VAC, 50 Hz supply. Cable, connector, guard and panel clearances still need the exact drawings.

Filter and pressure

For the example, the complete inlet-to-outlet path requires 3 mm H₂O of static pressure at about 40 CFM. Use this single matched airflow and pressure point to screen both curves. A real project needs data or measurements for its own filter and outlet.

Check the published 50 Hz curves

12025 AC · screening hold

On printed page 10, use the 50 Hz family trace for the candidate HB12025HA1B. At approximately 40 CFM the trace stays below the example target of 3 mm H₂O, despite the higher airflow number in the catalogue table. Hold this candidate for the stated duty. Open page 10.

12038-7P AC · candidate for verification

On printed page 12, the 50 Hz family trace is above the target near 40 CFM. The ball-bearing HB12038HA1B-7P is a candidate for follow-up. Its outline has 38 ± 0.5 mm fan-body depth, so check mounting, connector clearance and the exact suffix curve before ordering. Open page 12.

Decide what the installed sample must show

Mechanical and electrical checks

Confirm the full suffix and drawing revision, then check fasteners, cover and cable clearance in the actual installation. Keep supply frequency and the complete filter and outlet arrangement in the record.

Airflow and temperature checks

Measure airflow by a method appropriate for the complete cabinet and confirm the relevant component temperatures under the specified load and ambient condition. If a used filter is part of the service requirement, specify and verify that condition separately.

Result for this example

Carry the 12038-7P forward for a model-specific curve and equipment test. The example records a catalogue screening decision and leaves the installed result to the equipment test.

Apply the same checks to your cabinet

Send the heat load, inlet temperature, available space, supply, filter arrangement and required airflow at pressure. Include the exact model and the document you need for the next decision.